Low voltage feeder monitoring device - monitoring module
1.Product profile
The low-voltage feeder monitoring device consists of a communication unit, a power module, and a monitoring unit. The communication unit is generally installed in the distribution cabinet, column mounted JP cabinet, or low-voltage cable branch box. It serves as a data aggregation gateway to achieve upstream communication through carrier modules, communicate with downstream monitoring units through CAN bus, and achieve local maintenance of the system through Bluetooth interface. The number of monitoring units that can be connected is not less than 64; The power module provides DC power, CAN bus, and sampling voltage to the monitoring unit through a cascaded interface. A single power module can be connected to no less than 10 monitoring units; The monitoring unit is connected to an external current transformer to achieve current detection function, connected to the voltage sampling signal output by the power module to achieve voltage detection function, connected to a switch input to achieve station status monitoring, with functions such as topology characteristic signal transmission, characteristic signal analysis, and phase sequence recognition.
2.Product specifications
performance parameters |
performance indicators |
accuracy class |
Voltage: ≤±0.5%. |
Current: ≤±0.5%; |
Active power: ≤±1%; reactive power: ≤±2%; |
Power factor: ≤±1%; apparent power: ≤±2%; |
Power: ≤± 1%; Frequency: ≤± 0.01Hz |
Wiring method |
Three-phase, four-wire |
Input current |
Measuring range |
0~250A , 0~ 400A, 0~600A |
Operating power supply |
Rated voltage |
DC12V, allowable deviation -10%~+20 |
Power consumption |
The monitoring unit consumes no more than 40mA of current when powered by DC12V |
Communications |
communication protocols |
DL/T645-2007 |
Reset |
Hardware |
Press and hold (>3s) the reset button for hardware reset, the |
Software |
software remote reset |
environmental conditions |
ambient temperature, humidity |
Temperature range: -40~+70°C |
Maximum rate of temperature change: 1.0°C/min |
Relative humidity: 10 to 100% |
Maximum absolute humidity: 35g/m³ |
the environment in which it is used |
free from explosive hazards, corrosive gases and conductive dust, the presence of severe mold, and sources of severe vibration and shock |
storage temperature |
-40ºC~80ºC |
clock accuracy |
Daily error |
The monitoring unit and the communication unit in the low-voltage feeder monitoring device shall realize high-precision timing, and the timing accuracy shall be not less than 20ms, and can receive the clock calling and timing commands from the upstream equipment |
3.Selection specifications
function module |
Serial number |
function point |
function point descriptions |
The monitoring module |
real-time measurements |
1 |
phase voltage |
Phase voltages: Ua, Ub, Uc |
√ |
2 |
line voltage |
Line voltage: Uab, Ubc, Uca |
√ |
3 |
phase currents |
Phase currents: Ia, Ib, Ic |
√ |
4 |
Active power |
Active power: Pa, Pb, Pc, P |
√ |
5 |
Reactive power |
Reactive power: Qa, Qb, Qc, Q |
√ |
6 |
apparent power |
Apparent power: Sa, Sb, Sc, S |
√ |
7 |
Power factor |
Power factor: Pfa, Pfb, Pfc, Pf |
√ |
8 |
Phase |
Voltage/current: ∠Ua, ∠Ub, ∠Uc |
√ |
9 |
Frequency |
System frequency: F |
√ |
Electricity metering |
10 |
Active Electricity |
Split-phase and combined-phase bi-directional active energy |
√ |
11 |
reactive power meters |
Split-phase and combined-phase bi-directional reactive energy |
√ |
12 |
The view is in the electric degree |
Split-phase and combined-phase visual energy |
√ |
Freeze |
13 |
load records |
Recorded every 5 minutes for 7 days, with cyclic coverage that |
√ |
Clock |
14 |
Clock |
With hardware precision clock |
√ |
Current transformers |
15 |
Supporting external current transformers |
Equipped with 250A/50mA, 400A/80mA, 600A/120mA transformers |
√ |
phase sequence identification |
16 |
With its own positive phase sequence, reverse phase sequence monitoring and phase sequence recognition function |
√ |
topology identification |
17 |
with hardware topology recognition, injection and acquisition of characteristic signals from B-phase loops |
√ |
data logging |
18 |
All volumes should be stored locally for a period of not less than 7 days |
√ |
Telemetry |
19 |
Incoming and outgoing |
With 2-way open-in telemetry status |
√ |
communication interface |
20 |
debugging interface |
Support 1 RS485 interface for product debugging |
√ |
Note: "√" indicates that this function is standard, "○" indicates that this function is optional |
4.Product installation and schematic diagram
5.About our service
* We could provide 7* 24-hour phone call after-sales service.
* We provide a 2-year guarantee time and will change the meter for you within 1 year if there's something wrong with the product. Except for natural disasters or man-made reasons.
* Recommend the most advanced application technology and management model in the industry to customers, and provide customers with detailed solutions.
6.Package and ship