Customization: | Available |
---|---|
After-sales Service: | Two Years |
Warranty: | Two Years |
Still deciding? Get samples of US$ 125/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
performance parameter | Performance index | |
accuracy class | Voltage: ≤ 1%; Current: ≤ 1%; Active power: ≤ 1%; Reactive power: ≤ 1%; Power factor: ≤ 1%; Apparent power: ≤ 1%; Electricity quantity: ≤ 1%; Frequency: ≤± 0.02Hz | |
Connection mode | Three-phase four wire | |
input voltage | rated voltage | Three-phase four-wire system: 3×57.7/100V, 3× 220/380 V. |
frequency range | 45~65Hz | |
measuring range | 0.1U~1.2Un | |
incoming current | rated current | AC5A |
frequency range | 45~65HZ | |
measuring range | 0.02-1.2In | |
working power supply | rated voltage | AC 220V (allowable deviation -20%~+20%) |
Power consumption | ≤ 5W, 10VA | |
communication interface | RS485 communication | 1200bps,2400bps,4800bps,9600bps,115200 |
environmental conditions | Ambient temperature and humidity | Temperature range:-40 ~+70ºC |
Maximum temperature change rate: 1.0ºC/ min | ||
Relative humidity: 10 ~ 100% | ||
Maximum absolute humidity: 35g/m, at an altitude of 2000m. | ||
operational environment | There is no explosion danger, corrosive gas and conductive dust, serious mold and violent vibration shock source. | |
storage temperature | -40ºC~80ºC | |
Daily error | ≤2 seconds/day, supporting communication timing. | |
mechanical character | vibrate | GB/T 11287 severity level 1 |
lash | GB/T 14537 severity level 1 | |
collide | GB/T 14537 severity level 1 | |
Electromagnetic compatibility performance | Radio frequency electromagnetic field immunity test | GB/T 17626.3-2006 Severity Grade 4 |
Fast transient pulse group test | GB/T 17626.4-2008 Severity Grade 4 | |
Attenuated oscillation wave immunity test | Severity grade 4-12-1998 | |
Electrostatic discharge test | GB/T 17626.2-2006 Severity Grade 3 | |
Surge immunity | GB/T 17626.5-2008 Severity Grade 4 | |
Radio frequency conduction immunity | GB/T 17626.6-2008 Severity Grade 3 | |
radio disturbance | GB/T 17215.211-2006 7.5.8 Class B Equipment | |
Interference degree of power frequency magnetic field | GB/T 17626.8-2006 400A/m | |
Electrical insulation performance | insulance | GBT 13729-2002, not less than 500MΩ ω. |
dielectric strength | GB/T 13729-2002, power frequency voltage 2kV, 1 minute. | |
surging | GB/T 13729-2002,1.2/50μs,5kV | |
measure | Height * width * depth | 115mm*65mm*67mm |
functional module | serial number | Function point | Function point description | Air conditioning soft control device |
Downlink communication | 1 | Air conditioning communication interface | 485 interface of 1-way water-cooled air-cooled central air conditioner | √ |
1-way VRV air conditioner CAN interface | ||||
1-way VRV air conditioner HOMBUS interface | ||||
1-way VRV air conditioner 485 interface | ||||
Uplink communication | 2 | modbus | Support custom point table | √ |
3 | mqtt | Support custom point table | ○ | |
4 | HPLC | Carrier communication | ○ | |
5 | 645 protocol | State Grid Edition 645 | √ | |
show | 6 | LCD display | Chinese display | √ |
7 | LED indicators (4) | Operation, carrier, uplink, downlink | √ | |
8 | button | Scroll down/up/back/confirm | √ | |
Protocol library | 9 | Water-cooled air cooling unit | Support various types of air conditioners from common mainstream manufacturers. | √ |
10 | Vrv air conditioning unit | Support various types of air conditioners from common mainstream manufacturers. | √ | |
Maintenance function | 11 | upgrade | Support Bluetooth upgrade program, support failure rollback. | √ |
12 | Parameter reading and writing | It has the function of reading and modifying parameters through RS485 communication interface; | √ | |
15 | Bluetooth | Support mobile phone Bluetooth APP connection, mobile phone Bluetooth+WeChat applet operation. | √ | |
Power Supply | 16 | auxiliary power supply | Support standby power supply | √ |
Real-time measurement | 17 | phase voltage | Phase voltage: Ua, Ub, Uc | √ |
18 | line voltage | Line voltage: Uab, Ubc, Uca | √ | |
19 | phase current | Phase current: Ia, Ib, Ic | √ | |
20 | active power | Active power: Pa, Pb, Pc, p. | √ | |
21 | wattless power | Reactive power: Qa, Qb, Qc and Q. | √ | |
22 | apparent power | Apparent power: Sa, Sb, Sc, s | √ | |
23 | power factor | Power factor: Pfa, Pfb, Pfc, Pf | √ | |
24 | frequency | System frequency: f | √ | |
Electricity measurement | 25 | Total electric energy | Positive and negative active and reactive power | √ |
safe | 26 | Hardware encryption | Optional ESAM module supports hardware encryption. | ○ |
Note: "√" marks this function as standard, and "○" indicates that this function is optional. |