Customization: | Available |
---|---|
After-sales Service: | Two Years |
Warranty: | Two Years |
Still deciding? Get samples of US$ 610/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
performance parameter | Performance index | |
working power supply | Operating voltage range | AC 85V~264V |
Power consumption | <2.5W,5VA | |
environmental conditions | Working temperature | -20ºC~70ºC |
storage temperature | -40ºC~70ºC | |
Working humidity | 0 ~ 95% does not condense. | |
atmospheric pressure | 86kPa~106kPa | |
mechanical character | vibrate | GB/T 11287 severity level 1 |
lash | GB/T 14537 severity level 1 | |
collide | GB/T 14537 severity level 1 | |
Electromagnetic compatibility performance | Radio frequency electromagnetic field immunity test | GB/T 17626.3-2006 Severity Grade 3 |
Electrical fast transient test | GB/T 17626.4-2008 Severity Grade 4 | |
Attenuated oscillation wave immunity test | Severity grade 3-12-1998 | |
Electrostatic discharge test | GB/T 17626.2-2006 Severity Grade 3 | |
Surge immunity | GB/T 17626.5-2008 Severity Grade 3 | |
Radio frequency conduction immunity | GB/T 17626.6-2008 Severity Grade 3 | |
radio disturbance | GB/T 17215.211-2006 7.5.8 Class B Equipment | |
Interference degree of power frequency magnetic field | GB/T 17626.8-2006 Severity Grade 3 | |
Electrical insulation performance | insulance | GBT 13729-2002, not less than 100MΩ. |
dielectric strength | GB/T 13729-2002, power frequency voltage 2kV, 1 minute. | |
surging | GB/T 13729-2002,1.2/50μs,5kV |
performance parameter | Performance index | |
working power supply | operating voltage | DC24V |
Power consumption | <0.25W | |
communication interface | Communication baud rate | 9600bps |
Branch cable temperature monitoring | degree of accuracy | ±2ºC |
resolution ratio | 0.1ºC | |
range | 0ºC ~ 70ºC | |
Monitoring of live state of branch cable | Monitoring distance | 0.5~1cm |
Monitoring range | 85V~380V(AC) |
functional module | S/N | Function point | Function Point Description | Branch measuring unit |
Collector | ||||
communication interface | 1 | POWER BUS | Support 5-way slave | √ |
2 | RS485 | Support MODBUS-RTU protocol | √ | |
Communication interface with fusion terminal | 3 | Interface form | RS485 | √ |
4 | Mailing address range | 1~247 | √ | |
5 | Communication protocol | Modbus-RTU | √ | |
6 | Baud rate | 9600bps | √ | |
Communication interface with sensor | 7 | Interface form | POWER BUS | √ |
8 | Mailing address range | 1~247 | √ | |
9 | Communication protocol | Modbus-RTU | √ | |
10 | Baud rate | 9600bps | √ | |
Note: "√" mark is equipped with this function as standard, and "○" means this function is optional |
functional module | serial number | Function point | Function point description | Branch measuring unit |
sensor | ||||
Real-time measurement | 1 | Branch cable temperature monitoring | Temperature range: 0ºC ~ +70ºC | √ |
Voltage monitoring | 2 | Monitoring of live state of branch cable | Monitoring live voltage range: 85V~380V(AC) | √ |
communication interface | 3 | Interface form | POWER BUS | √ |
Address range | 1~15 | √ | ||
protocol | Modbus-RTU | √ | ||
Note: The "√" sign comes standard with this function, and "○" indicates that this function is optional. |