Customization: | Available |
---|---|
After-sales Service: | Two Years |
Warranty: | Two Years |
Still deciding? Get samples of US$ 90/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
performance parameter | Performance index | |
accuracy class | Voltage: ≤ 0.5%; Current: ≤ 0.5%; Active power: ≤ 0.5%; Reactive power: ≤ 1%; Power factor: ≤ 0.5%; Apparent work | |
Rate: ≤ 1.0%; Electricity quantity: ≤ 0.5%; Frequency: ≤± 0.02Hz | ||
Connection mode | Three-phase four-wire/three-phase three-wire | |
input voltage | rated voltage | AC220V |
frequency range | 45~65HZ | |
measuring range | 154V~286V | |
incoming current | rated current | AC 5A |
frequency range | 45~65HZ | |
measuring range | 20mA~6A | |
working power supply | rated voltage | AC 220V (allowable deviation -20%~+20%) |
Power consumption | Not more than 3W, 5VA | |
Switch input | Input form | Dry node (internal DC24V) |
communication interface | Interface form | RS485, carrier module |
protocol | Modbus,DL/T645 | |
environmental conditions | Ambient temperature and humidity | Temperature range:-40 ~+70ºC |
Maximum temperature change rate: 1.0ºC/ min | ||
Relative humidity: 10 ~ 100% | ||
Maximum absolute humidity: 35g/m | ||
operational environment | There is no explosion danger, corrosive gas and conductive dust, serious mold and violent vibration shock source. | |
storage temperature | -40ºC~80ºC | |
Clock accuracy | Daily error | ≤0.5 seconds/day, supporting communication timing. |
functional module | serial number | Function point | Function point description | Terminal module |
LON823 | ||||
Real-time measurement | 1 | phase voltage | Phase voltage: Ua, Ub, Uc | √ |
2 | line voltage | Line voltage: Uab, Ubc, Uca | √ | |
3 | Voltage sequence component | Voltage sequence components: U1, U2, U0 | √ | |
4 | phase current | Phase current: Ia, Ib, Ic | √ | |
5 | active power | Active power: Pa, Pb, Pc, p. | √ | |
6 | wattless power | Reactive power: Qa, Qb, Qc and Q. | √ | |
7 | apparent power | Apparent power: Sa, Sb, Sc, s | √ | |
8 | Power factor | Power factor: Pfa, Pfb, Pfc, Pf | √ | |
9 | phase position | Voltage/current: ∠Ua, ∠Ub, ∠Uc, ∠Ia, ∠Ib, ∠Ic | √ | |
10 | frequency | System frequency: f | √ | |
Electricity measurement | 11 | Active power | Split-phase and combined-phase bidirectional active energy | √ |
12 | Reactive power | Split-phase and combined-phase bidirectional reactive power | √ | |
13 | Apparent electric degree | Split-phase and close-phase are in electric energy. | √ | |
freeze | 14 | Load record | Record once every 5 minutes for 7 days, and cover it circularly. | ○ |
remote signalling | 15 | Drive in and out | With open remote communication status. | √ |
clock | 16 | clock | Accurate clock with hardware | √ |
Switch input | 17 | Switch input | 4-way switch active node input | ○ |
communication interface | 18 | RS485 communication | Standard 1 RS485 communication, supporting MODBUS-RTU protocol; Support online upgrade program through RS485 interface. | √ |
19 | Carrier communication | Support a single-phase carrier module interface (DL/T645 protocol) | √ | |
20 | Debugging interface | One RS485 interface for product debugging. | ○ | |
21 | Bluetooth communication | Bluetooth 4.2 communication, which can be used for data transmission. | ○ | |
Current transformer | 22 | Support external current transformer | Configure 250/5A, 400/5A and 630A/5A transformers. | √ |
Note: "√" marks this function as standard, and "○" indicates that this function is optional. |