performance parameters |
performance indicators |
accuracy class |
U, I: 0.2 level, P, Q, PF: 0.5 level, F: ±0.01 HZ, active power: 0.5S level, reactive power: 2 level |
display mode |
LCD display |
Networking |
Three-phase, four-wire |
Input Voltage |
Rated voltage |
3×220/380V AC |
frequency range |
45~65Hz |
overload capacity |
1.2Un (continuous); 2Un (10s allowed) |
Measuring range |
0.5Un~1.2Un |
functional consumption |
< 0.3VA per phase |
Input current |
Rated current |
Direct access: 5 (80) A |
overload capacity |
1.2In (continuous); 20In (1s allowed) |
Measuring range |
0 to 1.2 Imax with a threshold of 20 mA |
functional consumption |
< 0.5VA per phase |
switching inputs |
input form |
Active wet node (external 220VAC ±20%) |
isolation voltage |
4000Vac rms |
switching outputs |
output form |
mechanical contacts |
voltage withstand between contact and coil |
AC250V/5A,DC30V/5A |
Built-in relay |
Maximum switching current |
80A |
communication interface |
interface form |
RS485, power infrared, wireless radio frequency |
communication protocols |
Modbus-RTU protocol, radio frequency protocol |
environmental conditions |
Operating Temperature |
-20ºC~70ºC |
storage temperature |
-40ºC~70ºC |
Operating humidity |
0 to 95% non-condensing |
Atmospheric pressure |
86kPa~106kPa |
mechanical properties |
Vibration |
GB/T11287 severity level 1 |
Impact |
GB/T14537 severity level 1 |
Collision |
GB/T14537 severity level 1 |
electromagnetic compatibility performance |
radio frequency electromagnetic field immunity test |
GB/T 17626.3-2006 severity level 3 |
Fast transient pulse group test |
GB/T 17626.4-2008 Severity level 4 |
Attenuated oscillatory wave immunity test |
GB/T 17626.12-1998 Severity level 3 |
electrostatic discharge test |
GB/T 17626.2-2006 severity level 4 |
Surge immunity |
GB/T 17626.5-2008 Severity level 4 |
RF conducted immunity |
GB/T 17626.6-2008 Severity level 3 |
radio interference |
GB/T 17215.211-2006 7.5.8 Class B equipment |
degree of interference with industrial frequency magnetic fields |
GB/T 17626.8-2006 severity level 3 |
electrical insulation properties |
insulation resistance |
GBT 13729-2002, not less than 100MΩ |
medium strength |
GBT 13729-2002, Industrial frequency voltage 2KV, 1 min |
Impulse voltage |
GBT 13729-2002,1.2/50μs,5KV |
Dimensions |
H*W*D |
126mm*97mm*79mm |
mounting method |
rail mounted |