function point |
function point descriptions |
LON521D |
LON521L |
LON521T |
protection functions |
Initiate timeout protection |
√ |
- |
- |
overload protection, overcurrent blocking protection, short circuit protection |
√ |
- |
- |
current imbalance protection, phase break protection |
√ |
- |
- |
ground fault synthesis computational protection |
√ |
√ |
- |
Leakage protection / ground fault real pick protection (need to be equipped with zero sequence current transformer / grounding current transformer) |
○ |
○ |
- |
(choose one or the other) |
(choose one or the other) |
underload protection |
√ |
- |
- |
overflow fault (fault current exceeding the breaking capacity of the contactor) trips the circuit breaker |
√ |
- |
- |
Overvoltage protection, undervoltage protection |
√ |
√ |
- |
frequency protection, under power factor protection |
√ |
- |
- |
Anti-Shake/Shake Restart |
○ |
- |
- |
External interlocks |
√ |
√ |
- |
tE time protection |
√ |
- |
- |
Electrical current interruption protection (low voltage blocking overcurrent section) |
- |
√ |
- |
Current-limited quick disconnect protection (low voltage blocking overcurrent II) |
- |
√ |
- |
Overcurrent protection (three stages of overcurrent) |
- |
√ |
- |
Overload protection |
- |
√ |
- |
Spring not storing energy alarm |
- |
√ |
- |
PT disconnection alarm |
- |
√ |
- |
PT disconnection protection |
- |
- |
√ |
Low-voltage one-, two- and three-phase protection (can be associated with PT disconnection, switching 1 blocking function) |
- |
- |
√ |
busbar overvoltage protection, zero sequence overvoltage protection |
- |
- |
√ |
Switching quantity 1 protection |
- |
- |
√ |
Switching 2 protection |
- |
- |
√ |
real-time measurements |
three-phase currents, grounding currents, three-phase current unbalance ratio |
√ |
√ |
- |
Leakage current/grounding actual pickup current |
○ |
○ |
- |
three-phase phase voltage, three-phase line voltage, frequency |
√ |
√ |
√ |
power factor, active power, reactive power, active energy, reactive energy |
√ |
√ |
- |
zero sequence voltage, positive sequence voltage, negative sequence voltage |
- |
√ |
√ |
Fault logging |
with 32 SOE recordings with 1s resolution |
√ |
√ |
√ |
switching inputs |
With 6-way DI, built-in power supply, external passive trunk node |
√ |
√ |
√ |
Relay Output |
With 3-way DO, AC 250/5A; DC 30V/5A |
√ |
√ |
√ |
analog output |
Optional 1-channel DC4~20mA analog variable output |
√ |
√ |
√ |
digital communications |
1 RS485 interface, support MODBUS-RTU protocol |
√ |
√ |
√ |
undervoltage restart |
With the voltage detection function module can realize the short-time under and voltage loss restart function |
√ |
- |
- |
protection parameter settings |
All kinds of protection fixed value query, adjusting |
√ |
√ |
√ |
system parameterization |
Parameterization of rated voltage, rated current, and communication address |
√ |
√ |
√ |
LED indication |
start, run, alarm/action, stop |
√ |
√ |
√ |
Note: "-" indicates that this function is not available, "○" indicates that this function is optional, and "√" indicates that this function is standard |