functional module |
S/N |
Function point |
Function Point Description |
Low voltage cable branch box monitoring unit |
real-time measurement |
1 |
Phase voltage |
Phase voltage: Ua, Ub, Uc |
√ |
2 |
Line voltage |
Line voltage: Uab, Ubc, Uca |
√ |
3 |
Voltage sequence component |
Voltage sequence components: U1, U2, U0 |
√ |
4 |
Phase current |
Phase current: Ia, Ib, Ic |
√ |
6 |
Active power |
Active power: Pa, Pb, Pc, P |
√ |
7 |
Reactive power |
Reactive power: Qa, Qb, Qc, Q |
√ |
8 |
Apparent power |
Apparent power: Sa, Sb, Sc, S |
√ |
9 |
power factor |
Power factor: Pfa, Pfb, Pfc, Pf |
√ |
10 |
phase |
Voltage/current: ∠ Ua, ∠ Ub, ∠ Uc, ∠ Ia, ∠ Ib, ∠ Ic |
√ |
11 |
frequency |
System frequency: F |
√ |
Electricity metering |
12 |
Active kilowatt hour |
Bi directional active electric energy of phase separation and phase combination |
√ |
13 |
Reactive kilowatt hour |
Two way reactive electric energy of phase separation and phase combination |
√ |
14 |
Apparent electric degree |
Apparent electric energy of phase separation and phase combination |
√ |
frozen |
15 |
Load record |
Record once every 5 minutes for 7 days, with cyclic coverage |
○ |
Power quality |
16 |
Harmonic content |
Harmonic content of three-phase voltage and current for 2~31 times |
√ |
17 |
Harmonic distortion rate |
Total, odd and even harmonic distortion rate |
√ |
18 |
out-off-balance |
Voltage and current imbalance |
√ |
exceed the time limit |
19 |
Over limit alarm |
Level 8 out of limit alarm function, which can monitor power parameters and remote signals, generate alarm when conditions are met, and can be linked with the output for alarm exit linkage |
√ |
Event record |
20 |
SOE record |
It has 64 SOE recording functions, including switch displacement, remote control, out of limit alarm, etc., with time mark recording |
√ |
21 |
Record of maximum value |
The maximum and minimum values of relevant parameters (phase/line voltage, current, active power, reactive power, apparent power, power factor, frequency, demand) can be counted in real time and recorded with time scale |
√ |
Clock |
22 |
Clock |
With hardware accurate clock |
√ |
I/O |
23 |
Switch input |
4-way switching value active node input |
○ |
24 |
Switching value output |
2-way passive switching value output, support level/pulse type, support remote control or serve as local threshold crossing alarm outlet |
○ |
communication interface |
25 |
RS485 communication |
Standard configuration: 1-way RS485 communication, supporting MODBUS-RTU protocol; Support online upgrade program through RS485 interface |
√ |
26 |
Carrier communication |
Support one channel single-phase carrier module interface (645 protocol) |
√ |
Current transformer |
27 |
External current transformer |
Incoming line is configured with 600A~100mA transformer |
√ |
The branch is configured with 400A~100mA transformer |
Note: "√" mark is equipped with this function as standard, and "○" means this function is optional |